A comparison between energy performance, simulated by means of the EnergyPlus building simulation program, of two air systems (all air and fan coil) and radiant heating and cooling loors/ceilings is developed in this work for various European climates (Milan, Frankfurt, London, Madrid, Athens, Helsinki, and Moscow) and carried out on a reference building selected from among U.S. Department of Energy commercial building new construction benchmarks. The comparison is focused on the analysis of energy sources and CO2 emissions at equivalent thermal comfort quality levels in the various cases. The adoption of a radiant system, and of an appropriate primary energy system, always results in a reduction of energy sources exploited, of costs for energy wares purchased, and of carbon dioxide emissions. The greatest reductions can be achieved in climates where the energy demand for cooling is greater than the energy demand for heating. The article also focuses on the discussion of the procedure to be adopted when a comparison between air systems and radiant systems is implemented.

Numerical comparison between energy and comfort performances of radiant heating and cooling systems vs. air systems

FABRIZIO, Enrico;
2012-01-01

Abstract

A comparison between energy performance, simulated by means of the EnergyPlus building simulation program, of two air systems (all air and fan coil) and radiant heating and cooling loors/ceilings is developed in this work for various European climates (Milan, Frankfurt, London, Madrid, Athens, Helsinki, and Moscow) and carried out on a reference building selected from among U.S. Department of Energy commercial building new construction benchmarks. The comparison is focused on the analysis of energy sources and CO2 emissions at equivalent thermal comfort quality levels in the various cases. The adoption of a radiant system, and of an appropriate primary energy system, always results in a reduction of energy sources exploited, of costs for energy wares purchased, and of carbon dioxide emissions. The greatest reductions can be achieved in climates where the energy demand for cooling is greater than the energy demand for heating. The article also focuses on the discussion of the procedure to be adopted when a comparison between air systems and radiant systems is implemented.
2012
18
4
692
708
FABRIZIO E.; CORGNATI S.P.; CAUSONE F.; FILIPPI M.
File in questo prodotto:
File Dimensione Formato  
Numerical comparison.pdf

Open Access dal 01/01/2014

Tipo di file: POSTPRINT (VERSIONE FINALE DELL’AUTORE)
Dimensione 260.47 kB
Formato Adobe PDF
260.47 kB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/2318/118416
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 41
  • ???jsp.display-item.citation.isi??? 32
social impact