In the framework of heating and cooling of buildings, the underground can be used as thermal energy storage to smooth the difference between production and demand. The heat transfer performances vary significantly depending on the type of soil where the plant is set up, but also with the water content and the presence of groundwater flow. A lab scale modelling aimed at the simulation of thermal energy storage behaviour in porous materials was begun by Giordano et al. (2013) in order to better design the field scale living lab set up in Torino (Giordano et al., 2016). In this work, an implementation of the laboratory device is proposed with a monitoring system made of a low-cost open-source electronic platform based on Arduino (R). With respect to the previous version, the heat sources have been replaced with small scale borehole heat exchangers fed by a heating bath circulator equipped with in/out temperature sensors and flow rate control. Temperature and moisture monitoring within the medium has been improved with new and more accurate sensors. In addition, load sensors have been set up below the box to monitor the moisture migration induced during the heat injection. All the sensors are read by Arduino (R) boards and shields thanks to on purpose scripts and the data are monitored by a lab PC.

The use of open-source electronic platforms to monitor the efficiency of Borehole Thermal Energy Storage Systems (BTES) in porous materials by means of lab scale modeling

Chicco J;Giordano N;Mandrone G
2018-01-01

Abstract

In the framework of heating and cooling of buildings, the underground can be used as thermal energy storage to smooth the difference between production and demand. The heat transfer performances vary significantly depending on the type of soil where the plant is set up, but also with the water content and the presence of groundwater flow. A lab scale modelling aimed at the simulation of thermal energy storage behaviour in porous materials was begun by Giordano et al. (2013) in order to better design the field scale living lab set up in Torino (Giordano et al., 2016). In this work, an implementation of the laboratory device is proposed with a monitoring system made of a low-cost open-source electronic platform based on Arduino (R). With respect to the previous version, the heat sources have been replaced with small scale borehole heat exchangers fed by a heating bath circulator equipped with in/out temperature sensors and flow rate control. Temperature and moisture monitoring within the medium has been improved with new and more accurate sensors. In addition, load sensors have been set up below the box to monitor the moisture migration induced during the heat injection. All the sensors are read by Arduino (R) boards and shields thanks to on purpose scripts and the data are monitored by a lab PC.
2018
46
155
160
Arduino (R), heat transfer, lab scale modeling, thermal conductivity
Chicco J, Giordano N, Mandrone G
File in questo prodotto:
File Dimensione Formato  
Chicco et alii 2018 ROL SGI.pdf

Accesso riservato

Tipo di file: PDF EDITORIALE
Dimensione 1.23 MB
Formato Adobe PDF
1.23 MB Adobe PDF   Visualizza/Apri   Richiedi una copia